Hospital water system linked to Mycobacterium abscessus cluster

  • By

  • Meg Barbor

  • October 6, 2026

  • 4 min

Share

Objective:

Investigate a 2024 cluster of Mycobacterium abscessus cases at a Maryland hospital and identify potential environmental sources. To investigate a cluster of Mycobacterium abscessus cases at a Maryland hospital, identify potential environmental sources and assess mitigation measures.

Approach:
  • : Investigators reviewed clinical and epidemiologic data for 10 patients with positive cultures collected between March 2023 and June 2024. An additional patient was identified in September 2024.
  • : Before mitigation, investigators collected 47 environmental samples from 19 hospital locations, including bulk water and swabs from faucets, sinks and ice machines.
  • : Whole-genome sequencing compared patient and environmental isolates. Follow-up sampling assessed mitigation measures.
Key Findings:
  • Six patients were classified as having clinical infections; five likely represented colonization or specimen contamination.
  • M. abscessus grew from 18 of 47 environmental samples (38%) and was detected throughout the hospital, including in ice machines.
  • Four of five genetic subclusters contained both patient and environmental isolates. One patient isolate exactly matched a sample from a postanesthesia care unit ice machine; two other patient isolates were closely related to environmental samples from the same area.
  • Sequencing and epidemiologic findings confirmed hospital water system colonization and implicated ice machines as a probable infection source.
  • M. abscessus remained detectable after hospital-wide flushing and increased disinfectant levels. Follow-up samples from locations with point-of-use filters showed no bacterial growth.
  • One patient died within 60 days of the first positive culture, but the death was not attributed to M. abscessus.
Interpretation:

The investigation linked the patient cluster to contamination of the hospital water system, with ice machines identified as a probable source. The authors noted that M. abscessus can be difficult to eliminate once biofilm develops. The investigation linked the cluster to the hospital water system, with ice machines implicated as a probable source. Point-of-use filters appeared most effective, while flushing and increased disinfectant levels appeared to produce only temporary reductions.

Limitations:
  • Ice machines were implicated as a probable source rather than definitively established as the source.
  • Point-of-use filters are expensive and require regular inspection and replacement.
  • The supplied article does not describe additional study limitations.
Conclusion:

The hospital updated its water management plan to include more frequent flushing, residual disinfectant testing and specific testing for M. abscessus. The authors emphasized water management and sink-safety education. The hospital expanded its water management plan to include more frequent flushing, residual disinfectant testing and M. abscessus testing. Investigators emphasized swift removal of potential exposure sources, robust water management and sink-safety education.